cimpy.cgmes_v2_4_15.PssIEEE2B module

class cimpy.cgmes_v2_4_15.PssIEEE2B.PssIEEE2B(inputSignal1Type=None, inputSignal2Type=None, vsi1max=0.0, vsi1min=0.0, tw1=0, tw2=0, vsi2max=0.0, vsi2min=0.0, tw3=0, tw4=0, t1=0, t2=0, t3=0, t4=0, t6=0, t7=0, t8=0, t9=0, t10=0, t11=0, ks1=0.0, ks2=0.0, ks3=0.0, n=0, m=0, vstmax=0.0, vstmin=0.0, *args, **kw_args)[source]

The class represents IEEE Std 421.5-2005 type PSS2B power system stabilizer model. This stabilizer model is designed to represent a variety of dual-input stabilizers, which normally use combinations of power and speed or frequency to derive the stabilizing signal. Reference: IEEE 2B 421.5-2005 Section 8.2.

inputSignal1Type

Type of input signal #1. Typical Value = rotorSpeed. Default: None

inputSignal2Type

Type of input signal #2. Typical Value = generatorElectricalPower. Default: None

vsi1max

Input signal #1 max limit (Vsi1max). Typical Value = 2. Default: 0.0

vsi1min

Input signal #1 min limit (Vsi1min). Typical Value = -2. Default: 0.0

tw1

First washout on signal #1 (Tw1). Typical Value = 2. Default: 0

tw2

Second washout on signal #1 (Tw2). Typical Value = 2. Default: 0

vsi2max

Input signal #2 max limit (Vsi2max). Typical Value = 2. Default: 0.0

vsi2min

Input signal #2 min limit (Vsi2min). Typical Value = -2. Default: 0.0

tw3

First washout on signal #2 (Tw3). Typical Value = 2. Default: 0

tw4

Second washout on signal #2 (Tw4). Typical Value = 0. Default: 0

t1

Lead/lag time constant (T1). Typical Value = 0.12. Default: 0

t2

Lead/lag time constant (T2). Typical Value = 0.02. Default: 0

t3

Lead/lag time constant (T3). Typical Value = 0.3. Default: 0

t4

Lead/lag time constant (T4). Typical Value = 0.02. Default: 0

t6

Time constant on signal #1 (T6). Typical Value = 0. Default: 0

t7

Time constant on signal #2 (T7). Typical Value = 2. Default: 0

t8

Lead of ramp tracking filter (T8). Typical Value = 0.2. Default: 0

t9

Lag of ramp tracking filter (T9). Typical Value = 0.1. Default: 0

t10

Lead/lag time constant (T10). Typical Value = 0. Default: 0

t11

Lead/lag time constant (T11). Typical Value = 0. Default: 0

ks1

Stabilizer gain (Ks1). Typical Value = 12. Default: 0.0

ks2

Gain on signal #2 (Ks2). Typical Value = 0.2. Default: 0.0

ks3

Gain on signal #2 input before ramp-tracking filter (Ks3). Typical Value = 1. Default: 0.0

n

Order of ramp tracking filter (N). Typical Value = 1. Default: 0

m

Denominator order of ramp tracking filter (M). Typical Value = 5. Default: 0

vstmax

Stabilizer output max limit (Vstmax). Typical Value = 0.1. Default: 0.0

vstmin

Stabilizer output min limit (Vstmin). Typical Value = -0.1. Default: 0.0

Documentation of parent class PowerSystemStabilizerDynamics:

Power system stabilizer function block whose behaviour is described by reference to a standard model

RemoteInputSignal

Remote input signal used by this power system stabilizer model. Default: “list”

ExcitationSystemDynamics

Excitation system model with which this power system stabilizer model is associated. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects

The domain object to which this diagram object is associated. Default: “list”

mRID

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

shortName

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

cgmesProfile

alias of cimpy.cgmes_v2_4_15.Base.Profile

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.PssIEEE2B