cimpy.cgmes_v2_4_15.GovHydroR module¶
-
class
cimpy.cgmes_v2_4_15.GovHydroR.
GovHydroR
(mwbase=0.0, pmax=0.0, pmin=0.0, r=0.0, td=0, t1=0, t2=0, t3=0, t4=0, t5=0, t6=0, t7=0, t8=0, tp=0, velop=0.0, velcl=0.0, ki=0.0, kg=0.0, gmax=0.0, gmin=0.0, tt=0, inputSignal=False, db1=0.0, eps=0.0, db2=0.0, tw=0, at=0.0, dturb=0.0, qnl=0.0, h0=0.0, gv1=0.0, pgv1=0.0, gv2=0.0, pgv2=0.0, gv3=0.0, pgv3=0.0, gv4=0.0, pgv4=0.0, gv5=0.0, pgv5=0.0, gv6=0.0, pgv6=0.0, *args, **kw_args)[source]¶ Fourth order lead-lag governor and hydro turbine.
- mwbase
Base for power values (MWbase) (>0). Unit = MW. Default: 0.0
- pmax
Maximum gate opening, PU of MWbase (Pmax). Typical Value = 1. Default: 0.0
- pmin
Minimum gate opening, PU of MWbase (Pmin). Typical Value = 0. Default: 0.0
- r
Steady-state droop (R). Typical Value = 0.05. Default: 0.0
- td
Input filter time constant (Td). Typical Value = 0.05. Default: 0
- t1
Lead time constant 1 (T1). Typical Value = 1.5. Default: 0
- t2
Lag time constant 1 (T2). Typical Value = 0.1. Default: 0
- t3
Lead time constant 2 (T3). Typical Value = 1.5. Default: 0
- t4
Lag time constant 2 (T4). Typical Value = 0.1. Default: 0
- t5
Lead time constant 3 (T5). Typical Value = 0. Default: 0
- t6
Lag time constant 3 (T6). Typical Value = 0.05. Default: 0
- t7
Lead time constant 4 (T7). Typical Value = 0. Default: 0
- t8
Lag time constant 4 (T8). Typical Value = 0.05. Default: 0
- tp
Gate servo time constant (Tp). Typical Value = 0.05. Default: 0
- velop
Maximum gate opening velocity (Velop). Unit = PU/sec. Typical Value = 0.2. Default: 0.0
- velcl
Maximum gate closing velocity (Velcl). Unit = PU/sec. Typical Value = -0.2. Default: 0.0
- ki
Integral gain (Ki). Typical Value = 0.5. Default: 0.0
- kg
Gate servo gain (Kg). Typical Value = 2. Default: 0.0
- gmax
Maximum governor output (Gmax). Typical Value = 1.05. Default: 0.0
- gmin
Minimum governor output (Gmin). Typical Value = -0.05. Default: 0.0
- tt
Power feedback time constant (Tt). Typical Value = 0. Default: 0
- inputSignal
Input signal switch (Flag). true = Pe input is used false = feedback is received from CV. Flag is normally dependent on Tt. If Tf is zero, Flag is set to false. If Tf is not zero, Flag is set to true. Typical Value = true. Default: False
- db1
Intentional dead-band width (db1). Unit = Hz. Typical Value = 0. Default: 0.0
- eps
Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0. Default: 0.0
- db2
Unintentional dead-band (db2). Unit = MW. Typical Value = 0. Default: 0.0
- tw
Water inertia time constant (Tw). Typical Value = 1. Default: 0
- at
Turbine gain (At). Typical Value = 1.2. Default: 0.0
- dturb
Turbine damping factor (Dturb). Typical Value = 0.2. Default: 0.0
- qnl
No-load turbine flow at nominal head (Qnl). Typical Value = 0.08. Default: 0.0
- h0
Turbine nominal head (H0). Typical Value = 1. Default: 0.0
- gv1
Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0. Default: 0.0
- pgv1
Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0. Default: 0.0
- gv2
Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0. Default: 0.0
- pgv2
Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0. Default: 0.0
- gv3
Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0. Default: 0.0
- pgv3
Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0. Default: 0.0
- gv4
Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0. Default: 0.0
- pgv4
Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0. Default: 0.0
- gv5
Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0. Default: 0.0
- pgv5
Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0. Default: 0.0
- gv6
Nonlinear gain point 6, PU gv (Gv6). Typical Value = 0. Default: 0.0
- pgv6
Nonlinear gain point 6, PU power (Pgv6). Typical Value = 0. Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- SynchronousMachineDynamics
Turbine-governor model associated with this synchronous machine model. Default: “list”
- AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects
The domain object to which this diagram object is associated. Default: “list”
- mRID
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- shortName
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’
-
cgmesProfile
¶ alias of
cimpy.cgmes_v2_4_15.Base.Profile