cimpy.cgmes_v2_4_15.GovSteamSGO module

class cimpy.cgmes_v2_4_15.GovSteamSGO.GovSteamSGO(mwbase=0.0, t1=0, t2=0, t3=0, t4=0, t5=0, t6=0, k1=0.0, k2=0.0, k3=0.0, pmax=0.0, pmin=0, *args, **kw_args)[source]

Simplified Steam turbine governor model.

mwbase

Base for power values (MWbase) (>0). Unit = MW. Default: 0.0

t1

Controller lag (T1). Default: 0

t2

Controller lead compensation (T2). Default: 0

t3

Governor lag (T3) (>0). Default: 0

t4

Delay due to steam inlet volumes associated with steam chest and inlet piping (T4). Default: 0

t5

Reheater delay including hot and cold leads (T5). Default: 0

t6

Delay due to IP-LP turbine, crossover pipes and LP end hoods (T6). Default: 0

k1

One/per unit regulation (K1). Default: 0.0

k2

Fraction (K2). Default: 0.0

k3

Fraction (K3). Default: 0.0

pmax

Upper power limit (Pmax). Default: 0.0

pmin

Lower power limit (Pmin). Default: 0

Documentation of parent class TurbineGovernorDynamics:

Turbine-governor function block whose behavior is described by reference to a standard model

SynchronousMachineDynamics

Turbine-governor model associated with this synchronous machine model. Default: “list”

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. Default: None

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects

The domain object to which this diagram object is associated. Default: “list”

mRID

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

shortName

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

cgmesProfile

alias of cimpy.cgmes_v2_4_15.Base.Profile

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.GovSteamSGO