cimpy.cgmes_v2_4_15.ExcST4B module

class cimpy.cgmes_v2_4_15.ExcST4B.ExcST4B(kpr=0.0, kir=0.0, ta=0, vrmax=0.0, vrmin=0.0, kpm=0.0, kim=0.0, vmmax=0.0, vmmin=0.0, kg=0.0, kp=0.0, thetap=0.0, ki=0.0, kc=0.0, xl=0.0, vbmax=0.0, vgmax=0.0, uel=False, lvgate=False, *args, **kw_args)[source]

Modified IEEE ST4B static excitation system with maximum inner loop feedback gain .

kpr

Voltage regulator proportional gain (Kpr). Typical Value = 10.75. Default: 0.0

kir

Voltage regulator integral gain (Kir). Typical Value = 10.75. Default: 0.0

ta

Voltage regulator time constant (Ta). Typical Value = 0.02. Default: 0

vrmax

Maximum voltage regulator output (Vrmax). Typical Value = 1. Default: 0.0

vrmin

Minimum voltage regulator output (Vrmin). Typical Value = -0.87. Default: 0.0

kpm

Voltage regulator proportional gain output (Kpm). Typical Value = 1. Default: 0.0

kim

Voltage regulator integral gain output (Kim). Typical Value = 0. Default: 0.0

vmmax

Maximum inner loop output (Vmmax). Typical Value = 99. Default: 0.0

vmmin

Minimum inner loop output (Vmmin). Typical Value = -99. Default: 0.0

kg

Feedback gain constant of the inner loop field regulator (Kg). Typical Value = 0. Default: 0.0

kp

Potential circuit gain coefficient (Kp). Typical Value = 9.3. Default: 0.0

thetap

Potential circuit phase angle (thetap). Typical Value = 0. Default: 0.0

ki

Potential circuit gain coefficient (Ki). Typical Value = 0. Default: 0.0

kc

Rectifier loading factor proportional to commutating reactance (Kc). Typical Value = 0.113. Default: 0.0

xl

Reactance associated with potential source (Xl). Typical Value = 0.124. Default: 0.0

vbmax

Maximum excitation voltage (Vbmax). Typical Value = 11.63. Default: 0.0

vgmax

Maximum inner loop feedback voltage (Vgmax). Typical Value = 5.8. Default: 0.0

uel

Selector (Uel). true = UEL is part of block diagram false = UEL is not part of block diagram. Typical Value = false. Default: False

lvgate

Selector (LVgate). true = LVgate is part of the block diagram false = LVgate is not part of the block diagram. Typical Value = false. Default: False

Documentation of parent class ExcitationSystemDynamics:

Excitation system function block whose behavior is described by reference to a standard model

SynchronousMachineDynamics

Synchronous machine model with which this excitation system model is associated. Default: None

PowerSystemStabilizerDynamics

Power system stabilizer model associated with this excitation system model. Default: None

PFVArControllerType1Dynamics

Power Factor or VAr controller Type I model associated with this excitation system model. Default: None

VoltageCompensatorDynamics

Voltage compensator model associated with this excitation system model. Default: None

DiscontinuousExcitationControlDynamics

Discontinuous excitation control model associated with this excitation system model. Default: None

UnderexcitationLimiterDynamics

Undrexcitation limiter model associated with this excitation system model. Default: None

PFVArControllerType2Dynamics

Power Factor or VAr controller Type II model associated with this excitation system model. Default: None

OverexcitationLimiterDynamics

Overexcitation limiter model associated with this excitation system model. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects

The domain object to which this diagram object is associated. Default: “list”

mRID

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

shortName

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

cgmesProfile

alias of cimpy.cgmes_v2_4_15.Base.Profile

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.ExcST4B