cimpy.cgmes_v2_4_15.OverexcLimX1 module

class cimpy.cgmes_v2_4_15.OverexcLimX1.OverexcLimX1(efdrated=0.0, efd1=0.0, t1=0, efd2=0.0, t2=0, efd3=0.0, t3=0, efddes=0.0, kmx=0.0, vlow=0.0, *args, **kw_args)[source]

Field voltage over excitation limiter.

efdrated

Rated field voltage (EFD). Typical Value = 1.05. Default: 0.0

efd1

Low voltage point on the inverse time characteristic (EFD). Typical Value = 1.1. Default: 0.0

t1

Time to trip the exciter at the low voltage point on the inverse time characteristic (TIME). Typical Value = 120. Default: 0

efd2

Mid voltage point on the inverse time characteristic (EFD). Typical Value = 1.2. Default: 0.0

t2

Time to trip the exciter at the mid voltage point on the inverse time characteristic (TIME). Typical Value = 40. Default: 0

efd3

High voltage point on the inverse time characteristic (EFD). Typical Value = 1.5. Default: 0.0

t3

Time to trip the exciter at the high voltage point on the inverse time characteristic (TIME). Typical Value = 15. Default: 0

efddes

Desired field voltage (EFD). Typical Value = 0.9. Default: 0.0

kmx

Gain (K). Typical Value = 0.01. Default: 0.0

vlow

Low voltage limit (V) (>0). Default: 0.0

Documentation of parent class OverexcitationLimiterDynamics:

Overexcitation limiter function block whose behaviour is described by reference to a standard model

ExcitationSystemDynamics

Excitation system model with which this overexcitation limiter model is associated. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects

The domain object to which this diagram object is associated. Default: “list”

mRID

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

shortName

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

cgmesProfile

alias of cimpy.cgmes_v2_4_15.Base.Profile

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.OverexcLimX1