cimpy.cgmes_v2_4_15.GovGAST module

class cimpy.cgmes_v2_4_15.GovGAST.GovGAST(mwbase=0.0, r=0.0, t1=0, t2=0, t3=0, at=0.0, kt=0.0, vmax=0.0, vmin=0.0, dturb=0.0, *args, **kw_args)[source]

Single shaft gas turbine.

mwbase

Base for power values (MWbase) (> 0). Default: 0.0

r

Permanent droop (R). Typical Value = 0.04. Default: 0.0

t1

Governor mechanism time constant (T1). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical Value = 0.5. Default: 0

t2

Turbine power time constant (T2). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of a the free power turbine of an aero-derivative unit, for example. Typical Value = 0.5. Default: 0

t3

Turbine exhaust temperature time constant (T3). Typical Value = 3. Default: 0

at

Ambient temperature load limit (Load Limit). Typical Value = 1. Default: 0.0

kt

Temperature limiter gain (Kt). Typical Value = 3. Default: 0.0

vmax

Maximum turbine power, PU of MWbase (Vmax). Typical Value = 1. Default: 0.0

vmin

Minimum turbine power, PU of MWbase (Vmin). Typical Value = 0. Default: 0.0

dturb

Turbine damping factor (Dturb). Typical Value = 0.18. Default: 0.0

Documentation of parent class TurbineGovernorDynamics:

Turbine-governor function block whose behavior is described by reference to a standard model

SynchronousMachineDynamics

Turbine-governor model associated with this synchronous machine model. Default: “list”

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. Default: None

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects

The domain object to which this diagram object is associated. Default: “list”

mRID

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

shortName

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

cgmesProfile

alias of cimpy.cgmes_v2_4_15.Base.Profile

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.GovGAST