cimpy.cgmes_v2_4_15.DiscExcContIEEEDEC1A module¶
-
class
cimpy.cgmes_v2_4_15.DiscExcContIEEEDEC1A.
DiscExcContIEEEDEC1A
(vtlmt=0.0, vomax=0.0, vomin=0.0, ketl=0.0, vtc=0.0, val=0.0, esc=0.0, kan=0.0, tan=0, tw5=0, vsmax=0.0, vsmin=0.0, td=0, tl1=0, tl2=0, vtm=0.0, vtn=0.0, vanmax=0.0, *args, **kw_args)[source]¶ The class represents IEEE Type DEC1A discontinuous excitation control model that boosts generator excitation to a level higher than that demanded by the voltage regulator and stabilizer immediately following a system fault. Reference: IEEE Standard 421.5-2005 Section 12.2.
- vtlmt
Voltage reference (). Typical Value = 1.1. Default: 0.0
- vomax
Limiter (). Typical Value = 0.3. Default: 0.0
- vomin
Limiter (). Typical Value = 0.1. Default: 0.0
- ketl
Terminal voltage limiter gain (). Typical Value = 47. Default: 0.0
- vtc
Terminal voltage level reference (). Typical Value = 0.95. Default: 0.0
- val
Regulator voltage reference (). Typical Value = 5.5. Default: 0.0
- esc
Speed change reference (). Typical Value = 0.0015. Default: 0.0
- kan
Discontinuous controller gain (). Typical Value = 400. Default: 0.0
- tan
Discontinuous controller time constant (). Typical Value = 0.08. Default: 0
- tw5
DEC washout time constant (). Typical Value = 5. Default: 0
- vsmax
Limiter (). Typical Value = 0.2. Default: 0.0
- vsmin
Limiter (). Typical Value = -0.066. Default: 0.0
- td
Time constant (). Typical Value = 0.03. Default: 0
- tl1
Time constant (). Typical Value = 0.025. Default: 0
- tl2
Time constant (). Typical Value = 1.25. Default: 0
- vtm
Voltage limits (). Typical Value = 1.13. Default: 0.0
- vtn
Voltage limits (). Typical Value = 1.12. Default: 0.0
- vanmax
Limiter for Van (). Default: 0.0
Documentation of parent class DiscontinuousExcitationControlDynamics:
Discontinuous excitation control function block whose behaviour is described by reference to a standard model .
- RemoteInputSignal
Remote input signal used by this discontinuous excitation control system model. Default: None
- ExcitationSystemDynamics
Excitation system model with which this discontinuous excitation control model is associated. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects
The domain object to which this diagram object is associated. Default: “list”
- mRID
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- shortName
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’
-
cgmesProfile
¶ alias of
cimpy.cgmes_v2_4_15.Base.Profile