cimpy.cgmes_v2_4_15.OverexcLimIEEE module

class cimpy.cgmes_v2_4_15.OverexcLimIEEE.OverexcLimIEEE(itfpu=0.0, ifdmax=0.0, ifdlim=0.0, hyst=0.0, kcd=0.0, kramp=0.0, *args, **kw_args)[source]

The over excitation limiter model is intended to represent the significant features of OELs necessary for some large-scale system studies. It is the result of a pragmatic approach to obtain a model that can be widely applied with attainable data from generator owners. An attempt to include all variations in the functionality of OELs and duplicate how they interact with the rest of the excitation systems would likely result in a level of application insufficient for the studies for which they are intended. Reference: IEEE OEL 421.5-2005 Section 9.

itfpu

OEL timed field current limiter pickup level (I). Typical Value = 1.05. Default: 0.0

ifdmax

OEL instantaneous field current limit (I). Typical Value = 1.5. Default: 0.0

ifdlim

OEL timed field current limit (I). Typical Value = 1.05. Default: 0.0

hyst

OEL pickup/drop-out hysteresis (HYST). Typical Value = 0.03. Default: 0.0

kcd

OEL cooldown gain (K). Typical Value = 1. Default: 0.0

kramp

OEL ramped limit rate (K). Unit = PU/sec. Typical Value = 10. Default: 0.0

Documentation of parent class OverexcitationLimiterDynamics:

Overexcitation limiter function block whose behaviour is described by reference to a standard model

ExcitationSystemDynamics

Excitation system model with which this overexcitation limiter model is associated. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects

The domain object to which this diagram object is associated. Default: “list”

mRID

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

shortName

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

cgmesProfile

alias of cimpy.cgmes_v2_4_15.Base.Profile

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.OverexcLimIEEE